SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
Seires
User Manual
Cable Type
Note [1]: For some models, the outer diameter of a single-core cable ranges
from 14 mm to 36 mm based on the label in the maintenance compartment.
Note [2]: For some models, when the OT/DT terminal is crimped as shown in
the following figure and the rubber baffle plate of the AC wiring terminal is 112
mm, the maximum conductor cross-sectional area of the single-core cable can
be 400 mm
Figure 5-8 Specifications of the Crimped OT/DT Terminal
Figure 5-9 Specification of the Rubber Baffle Plate
Table 5-2 PE cable specifications
Conductor Cross-Sectional Area S of
the AC Power Cable (Unit: mm
S > 35
Issue 03 (2021-09-30)
2
.
NO TE
● The cable diameter must comply with local cable standards. The factors that affect
cable selection include the rated current, cable type, routing mode, ambient
temperature, and maximum expected line loss.
● When the MBUS is used for communication, it is recommended that the multi-wire
cable be used. The maximum communication distance is 1000 m. If other types of AC
power cables are used, contact Huawei technical support.
Copyright © Huawei Technologies Co., Ltd.
Conductor Cross-
Sectional Area
Conductor Cross-Sectional Area S
2
)
the PE Cable (Unit: mm
S
≥ S/2
P
5 Electrical Connections
Cable Outer Diameter
2
)
of
P
38