Siemens FDA241 Mounting & Installation page 23

Aspirating smoke detector
Hide thumbs Also See for FDA241:
Table of Contents

Advertisement

Building Technologies
Fire Safety
Procedure
 A suitable external power unit is available.
 The aspirating smoke detector's housing cover is removed.
1. Before connecting the external power unit to the terminal block, check the
voltage provided by the power unit. Permissible value: DC 24 V ±4 V
2. Connect the power unit to the aspirating smoke detector(s) according to the
connection diagram shown.
 The external power unit is connected to the aspirating smoke detector(s).
See also
 External power unit and batteries [➙ 15]
firealarmresources.com
Installation
Connecting the external power unit
A6V10345654_h_en_--
4
23
2015-05-29