3 Useful Information
In communication mode, the current value at that time is transmitted.
Event (current value)
If the transmission type "Event" is selected, a threshold (absolute or percentage)
can be specified for each data point. Only if the value of the data point has
changed beyond this threshold is this is evaluated as an event and the new value
stored. New values of a data point overwrite the last stored value.
In communication mode, the last stored value is transmitted.
Event (any value)
All values that differ from the last stored value are stored in chronological order and
transmitted to the communication partner during the communication mode.
Since the HMI does not support the OPC UA function "HistoryRead" and only the
last value is always transferred, this transfer type has no advantage for this
example.
3.2.3

Transmission Mode of the Data Points

If you parameterize "Event (current value)" or "Event (any value)" as the
transmission type, you can additionally select a transmission mode for each data
point.
Figure 3-6: Transmission modes
Table 3-1: Differences between the transmission modes
Transmission mode
Buffered transmission
Unsolicited transfer
Securely Connecting RTU3041C to TeleControl Server Basic
Entry ID: 109739240,
V3.0,
The stored value of the data point is transmitted in the
next communication mode.
A value change of the datapoint (event) starts an
additional communication mode. The data point is
transmitted immediately.
In this application example, this is parameterized at the
memory bit "critFillLevel".
07/2021
Explanation
92