SUN2000-(12KTL-25KTL)-M5 Series
User Manual
Alarm
Alarm
ID
Name
2039
Output
overcurre
nt
2040
Output
DC
compone
nt
overhigh
2051
Abnorma
l residual
current
Issue 01 (2022-06-15)
Alarm
Possible Causes
Severity
Major
Cause ID = 1
The power grid
voltage drops
dramatically or the
power grid is short-
circuited. As a
result, the inverter
transient output
current exceeds the
upper threshold,
and protection is
triggered.
Major
Cause ID = 1
The DC component
of the inverter
output current
exceeds the upper
threshold.
Major
Cause ID = 1
The insulation
impedance of the
input side to PE
decreases when the
inverter is
operating.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Troubleshooting
1. The inverter monitors its external
operating conditions in real time and
automatically recovers after the fault
is rectified.
2. If the alarm persists and affects the
energy yield of the PV plant, check
whether the output is short-circuited.
If the fault cannot be rectified,
contact your dealer or Huawei
technical support.
1. The inverter monitors its external
operating conditions in real time and
automatically recovers after the fault
is rectified.
2. If the alarm persists and affects the
energy yield of the PV plant, contact
your dealer or Huawei technical
support.
1. If the alarm occurs accidentally, the
external power cable may be
abnormal temporarily. The inverter
automatically recovers after the fault
is rectified.
2. If the alarm persists or lasts a long
time, check whether the impedance
between the PV string and ground is
too low.