D Locating Insulation Resistance Faults - Huawei SUN2000 Series User Manual

Hide thumbs Also See for SUN2000 Series:
Table of Contents

Advertisement

SUN2000-(12KTL-25KTL)-M5 Series
User Manual
D
Locating Insulation Resistance Faults
If the ground impedance of a PV string connected to the inverter is too low, the
inverter generates a Low insulation resistance alarm.
The possible causes are as follows:
After the Low insulation resistance alarm is reported by the inverter, insulation
resistance fault location is automatically triggered.If the fault location is
successful, the location information is displayed on the Alarm details screen of
the Low insulation resistance alarm on the FusionSolar app.
Log in to the FusionSolar app, choose Alarm > Active alarm, select Low
insulation resistance to enter the Alarm details screen.
Figure D-1 Alarm details
Issue 01 (2022-06-15)
A short circuit has occurred between the PV array and the ground.
The ambient air of the PV array is damp and the insulation between the PV
array and the ground is poor.
Copyright © Huawei Digital Power Technologies Co., Ltd.

D Locating Insulation Resistance Faults

84