Fc91 (Alarm Code); Fd06 (Input Tb Status); Fd07 (Output Tb Status) - Toshiba DeviceNet Option DEV002Z-1 User Manual

Tosvert vf-as1/ps1 devicenet option function manual
Table of Contents

Advertisement

3.4.6.16. FC91 (Alarm code)

bit
Over current alarm
0
Inverter over load alarm
1
Motor over load alarm
2
Over heat alarm
3
Over voltage alarm
4
Under voltage of main power
5
(Reserved)
6
Under current alarm
7
Over torque alarm
8
OLr alarm
9
Cumulative run-time alarm
10
(Reserved)
11
(Reserved)
12
(Reserved)
13
Stop after instantaneous power off
14
Stop after LL continuance time
15

3.4.6.17. FD06 (Input TB Status)

bit
TB Name
0
F
1
R
2*
ST
3
RES
4
S1
5
S2
6
S3
7
S4
8
L1
9
L2
10
L3
11
L4
12
L5
13
L6
14
L7
15
L8
*
This function is reserved in VF-PS1.

3.4.6.18. FD07 (Output TB Status)

bit
TB Name
0
OUT1
1
OUT2
2
FL
3
OUT3
4
OUT4
5
R1
6
OUT5
7
OUT6
8
R2
9
R3
10
R4
11 - 15
-
Function
Function (Parameter)
Input TB Function select 1 (f111)
Input TB Function select 2 (f112)
Input TB Function select 3 (f113)
Input TB Function select 4 (f114)
Input TB Function select 5 (f115)
Input TB Function select 6 (f116)
Input TB Function select 7 (f117)
Input TB Function select 8 (f118)
Input TB Function select 9 (f119)
Input TB Function select 10 (f120)
Input TB Function select 11 (f121)
Input TB Function select 12 (f122)
Input TB Function select 13 (f123)
Input TB Function select 14 (f124)
Input TB Function select 15 (f125)
Input TB Function select 16 (f126)
Function (Parameter)
Output TB Function select 1 (f130)
Output TB Function select 2 (f131)
Output TB Function select 3 (f132)
Output TB Function select 4 (f133)
Output TB Function select 5 (f134)
Output TB Function select 6 (f135)
Output TB Function select 7 (f136)
Output TB Function select 8 (f137)
Output TB Function select 9 (f138)
Output TB Function select 10 (f168)
Output TB Function select 11 (f169)
-
- 26 -
0
1
Normal
Under alarm
Normal
Under alarm
Normal
Under alarm
Normal
Under alarm
Normal
Under alarm
Normal
Under alarm
-
-
Normal
Under alarm
Normal
Under alarm
Normal
Under alarm
Normal
Under alarm
-
-
-
-
-
-
-
Dec., Under stop Refer to f256 value
-
Dec., Under stop
0
OFF
0
OFF
E6581281
Note
"c" blinking
"l" blinking
"l" blinking
"h" blinking
"p" blinking
-
-
-
-
-
-
-
-
-
Refer to uvc value
1
ON
1
ON
-
-