Installation Space - LG multi V ARUN Series Installation Manual

Hide thumbs Also See for multi V ARUN Series:
Table of Contents

Advertisement

Installation Space

Individual Installation
n During the installation of the unit, consider service, inlet, and outlet and acquire the minimum space
as shown in the figures below.
Category
4 sides are
walls
Only 2 sides
are walls
Limitations on
the height of
the wall
(Refer to 4
side walls)
Installation Space
Front
Front
Front
Front
Front
Front
Front
Front
No limit to the height of the wall
Front
Front
• The height of the wall on the front side must be 1500mm or less.
• The height of the wall on the inlet side must be 500mm or less.
• There is no limit to the wall on the side.
• If the height of the walls on the front and the side are higher than the limit,
there must be additional space on the front and the side.
- Additional Space on the inlet side by 1/2 of h1.
- Additional Space on the front side by 1/2 of h2
- h
2
- h
1
No limit to the
height of the wall
= A(Actual height) - 1500
= B(Actual height) - 500
Installation Space
Case 1
Case 2
(10mm≤Si d e Space≤49mm)
(Si d e Space≥49mm)
A≥10
A≥50
B≥300
B≥100
C≥10
C≥50
D≥500
D≥500
A≥10
A≥50
B≥300
B≥100
C≥10
C≥50
D≥500
D≥500
E≥20
E≥100
A≥10
A≥50
B≥300
B≥100
C≥10
C≥50
D≥500
D≥500
E≥20
E≥100
F≥600
E≥500
A≥10
A≥50
B≥300
B≥100
C≥10
C≥50
D≥300
D≥100
E≥20
E≥100
F≥500
E≥500
A≥10
B≥300
A≥200
B≥300
E≥400
Installation Manual 15