WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of the
equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the
product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
Between Indoor and Master Outdoor unit
SODU
IDU
INTERNET DRY1 DRY2 GND 12V
A
B
A
B
B
3
4
3
4
The GND terminal at the main PCB is a '-' terminal for dry contact.
It is not the point to make ground connection.
• Make sure that terminal number of master and slave outdoor units are matched.(A-A,B-B)
Master
Outdoor Unit
A
3
4
SODU
IDU
INTERNET DRY1 DRY2 GND 12V
A
B
A
B
B
A
SODU
IDU
INTERNET DRY1 DRY2 GND 12V
A
B
A
B
B
A
Electrical Wiring
Master
Outdoor Unit
Slave
Outdoor Unit
Installation Manual 67