Test Run
Static pressure compensation mode
This function secures the air flow rate of ODU, in case static pressure has been applied like using duct at
fan
discharge of ODU.
n Static pressure compensation dip S/W setting method
High static pressure mode : Set DIP S/W
Static pressure compensation mode cancellation
Static pressure compensation mode setting
method
method
Set the DIP S/W ON
DIP switch OFF
Power Reset
Power Reset
Static pressure compensation mode is set
Static pressure compensation mode is cancelled
DIP Switch Settings
Warning : Please reset SVC (Heat Pump)/ Main PCB (Cooling only)before starting this function
Installation Manual 97