Current Output Characteristic - Mitsubishi Electric A1S66ADA User Manual

Table of Contents

Advertisement

3 SPECIFICATION

3.3.2 Current output characteristic

(m A)
20
15
10
5
0
0
Fig. 3.2 Current output characteristic graph
3 - 6
An example of current output characteristic graph when the offset and gain settings are
changed is shown in Fig. 3.2.
2)
1)
2000
Digital input value
[Example]
On the characteristic graphs 1) to 2), the analog output voltage will be as follows when
the digital input value is set to 1000 and 2000:
No.
Digital input value
1000
1)
2000
1000
2)
2000
The I/O conversion characteristic when the off set
value and gain value are set, as shown in the
table below, is shown in the figure at left.
1)
4000
2)
Analog output value
5 mA
10 mA
8 mA
12 mA
MELSEC-A
Offset value
Gain value
0 mA
20 mA
4 mA
20 mA
3 - 6