Appendix; Appendix1 Comparison With The Conventional Analog I/O Module (A1S63Ada) - Mitsubishi Electric A1S66ADA User Manual

Table of Contents

Advertisement

APPENDIX

APPENDIX

Appendix1 Comparison with the Conventional Analog I/O Module (A1S63ADA)

Comparison of specifications for A1S66ADA with those for the conventional analog I/O
module, A1S63ADA, is shown below.
Item
I/O characteristics
D/A
Maximum resolution
conversion
Resolution range
switching
Conversion speed
Offset/gain adjustment
No. of channels
I/O characteristics
A/D
Maximum resolution
conversion
Resolution range
switching
Conversion speed
Offset/gain adjustment
No. of channels
App - 1
A1S66ADA
Digital input
Analog output
0 to 4000
(12-bit binary)
-10 to 10V
0 to 20 mA
4 to 20 mA
Voltage 1.0 mV (when analog output range is set
to 1 V to 5 V)
Current 4 μA (when analog output range is set to
4 mA to 20 mA)
2 CH in batch
240 μs or below/2 CH
Adjust using the front knob
Perform on-line adjustment for the 2 CH in batch
2 channels
Analog input
Digital output
0 to 10 V
0 to 5 V
1 to 5 V
(12-bit binary)
-10 to 10 V
0 to 20 mA
4 to 20 mA
Voltage 1.0 mV (when analog input range is set
to 1 to 5 V)
Current 4 μA (when analog input range is set to 4
to 20 mA)
4 CH in batch
400 μs or below/4 CH
Adjust using the front knob of the module
Perform on-line adjustment for the 4 CH in batch
4 channels
Specification
Digital input
0 to 10 V
-4000 to 4000
0 to 5 V
-8000 to 8000
1 to 5 V
-12000 to12000
0 to 4000
0 to 8000
0 to 12000
Voltage 0.83 mV (when resolution is set to
1/12000)
Current 1.7 μA (when resolution is set to
1/12000)
1 ms/1 CH (when resolution is set to 1/4000)
2 ms/1 CH (when resolution is set to 1/8000)
3 ms/1 CH (when resolution is set to 1/12000)
Set using the front switch
Analog input
-10 to 10 V
0 to 4000
-20 mA to 20 mA
Voltage 0.83 mV (when resolution is set to
1/12000)
Current 3.33 μA (when resolution is set to
1/6000)
3 CH in batch (resolution)
Individual channels (current/voltage)
1 ms/1 CH (when resolution is set to 1/4000)
2 ms/1 CH (when resolution is set to 1/8000)
3 ms/1 CH (when resolution is set to 1/12000)
Set each channel individually using the module
MELSEC-A
A1S63ADA
Analog output
-10 to 10 V
4 to 20 mA
1 channel
Digital output
-4000 to 4000
-8000 to 8000
-12000 to 12000
-2000 to 2000
-4000 to 4000
-6000 to 6000
front switch
2 channels
App - 1
App.

Advertisement

Table of Contents
loading