Grounding
Use with the following ground terminals connected.
Terminal name
Application
Protective grounding
Guarantees product safety, and increases immunity to noise.
Functional grounding
Increases immunity to noise.
External wiring
■External devices
For external devices connected to a this product, use the one of which insulation between the interface circuit section to this
product and the hazardous voltage circuit section is reinforced (if the device internally has a hazardous voltage circuit
section).
■Reinforced insulation
Reinforced insulation means insulation having the following withstand voltage.
Rated voltage of hazardous voltage
150 VAC or less
300 VAC or less
(Overvoltage category , source: IEC 60664-1)
Surge withstand voltage (1.2/50s)
2500V
4000V