Building Technologies
CPS Fire Safety
Note: The value to set in the Vitality Timer depends on the type of network. The
following rule applies:
- In Cerloop network, the MK7022 already handles the vitality check, and the
DMS host does not receive the heartbeat messages. In this case, set the timer
value = 0.
- In NK8000 and CDI-Net networks, if the connection also includes the MK7022
Cerloop interface, leave the value = 0. In the case of a link without MK7022, the
vitality check is required and the timer should be set to a value > 0.
Select the CS440 node
1. Select Tools > Import in the Composer menu to start CS440 import.
a The software presents a browsing window to search for the file to import
(the CS440 metafile is expected).
2. Using standard Windows controls, do the following:
Locate the file.
Select it and click Open.
a In a few moments, the CS440 structure is imported, and the node is
represented in the Composer tree.
Note: The node is renamed to match the metafile name. To customise the name,
click the node text, type in a new name, and press ENTER.
Note: After the import procedure, by selecting the Import tab, a report page
displays. It contains the detailed logs of the latest import procedure, including any
added or removed objects.
Linking the CS440 to the Communication network
Link the CS440 node to the Cerloop, CDI-Net, or NK8000 network.
1. Expand the network folders until you reach the node that represents the net-
work that is physically connected to the CS440 (Cerloop, CDI-Net, or NK8000).
2. Select the CS440 node.
3. Drag and drop the CS440 node to the network node.
a When the link is established, a new node appears on the structure tree, and its
properties can be seen on the Node tab.
Note: The valid link position for Cerloop is always the same main node,
representing the entire loop. The valid link positions on CDI-Net/NK8000 units are
distributed along the subsystem lines.
Note: Composer helps you in recognising a valid link by showing a shortcut Link
icon
instead of the circle No-link icon
Configuring intrusion control units
Configuring a CS440
.
A6V10359489_a_en
2
37