2.6.1
2.6.2
Building Technologies
CPS Fire Safety
Note: The CZ12 configuration structure does not need to be entered again in
Composer when there is an existing DMS7000 or LMSmodular configuration. In
this case, you can import:
- Export metafile from DMS7000, a text file including all the DMS7000 point texts.
- LMSmodular database, specifically DB_PUL.DBF and a DB_SUB.DBF files.

Configuration checklist

Verify that you have satisfied the items needed in the first checklist before
proceeding to the configuration checklist that follows.
Items needed for configuration
The CZ12 parameter settings, which can be provided in three ways:
l
The DMS7000 metafile to import
The LMSmodular databases DB_PUL.DBF and DB_SUB.DBF to import
Complete information about the CZ12 configuration for Intrusion sector, as
well as the Groups and Addresses organisation, and parent/child
relationship.
The local address (111, 112, etc.).
l
The connection to the DMS: Cerloop, CDI-Net, or NK8000.
l
Note: The CDI-Net/NK8000 requires a serial line available on the gateway.
Plug-ins needed:
l
#350201
Note: Plug-ins are installed during the software setup procedure. You can check
that the Plug-ins are actually available using the Composer Plug-in Installer in the
DMS8000 start menu.
Configuration overview
1. Add the folder(s) required for identifying the location of the CZ12 in the project
structure tree.
2. Add the CZ12 system node to the new folder.
3. Set the CZ12 Local Address and Vitality Timer.
4. Do one of the following:
Import the DMS7000 or LMS database, if available.
Link the CZ12 to the communication network (Cerloop, CDI-Net, or
NK8000).
5. Repeat steps above for all the CZ12s in the project.

Configuration procedures

Adding the intrusion system folder
1. In the left-hand bar, click the Generic Template icon
a A new node is added to the project structure.
Configuring intrusion control units
Configuring a CZ12
.