 Motor used and switch setting
Motor
Mitsubishi Electric high-
performance energy-saving motor
with encoder
Mitsubishi Electric Vector control
dedicated motor
Mitsubishi standard motor with
encoder
Mitsubishi high-efficiency motor
with encoder
Mitsubishi Electric constant-torque
motor with encoder
Other manufacturer's motor with encoder
*1
Set according to the motor (encoder).
*2
Prepare the power supply (5 V/12 V/15 V/24 V) for the encoder according to the encoder's output voltage.
*3
When the encoder output is the differential line driver type, only 5 V can be input.
NOTE
• Switch "SW2" is for manufacturer setting. Do not change the setting.
• When power is not supplied to the control circuit of the inverter, also turn OFF the encoder's power supply. Otherwise, the
plug-in option may be damaged.
16
INSTALLATION AND WIRING
Encoder specification
selection switch (SW3)
SF-PR-SC
Complementary
SF-V5RU
Complementary
SF-THY
Complementary
SF-JR
Differential
SF-HR
Differential
*1
Other
SF-JRCA
Differential
SF-HRCA
Differential
*1
Other
*1
Terminating resistor
selection switch (SW1)
OFF
OFF
OFF
ON
ON
*1
ON
ON
*1
*1
Power
*2
specifications
12V to 24V
12V to 24V
12 to 24 V
5V
5V
*2*3
5V
5V
*1*3
*1*3