Input Power Supply Lines; Figure 11 Example Of A Power Supply Connection When A Power Distribution Unit Is Not Used; Figure 12 Dual-Line Power Supply (When Connecting To Power Sockets) - Fujitsu ETERNUS AF250 S2 Site Planning Manual

Hide thumbs Also See for ETERNUS AF250 S2:
Table of Contents

Advertisement

1.
ETERNUS AF Installation
Outlet/Socket Specifications
For Direct (No Power Distribution Unit) Connections
The following diagram shows a power supply connection example when no power distribution units are used.

Figure 11 Example of a Power Supply Connection When a Power Distribution Unit Is Not Used

CP
PSU:
Power Supply Unit
CP:
Circuit Protector

Input Power Supply Lines

Multiple power supply facilities in the building or multiple UPS units are recommended for power supply redun-
dancy. A redundant configuration is used for the power supply of the ETERNUS AF. Business can continue even if
one of the power supply lines fails.
However, a single power supply facility configuration is also allowed for the entire system optimization (includ-
ing the server). When selecting a single configuration, take into consideration the availability of the system.

Figure 12 Dual-Line Power Supply (When Connecting to Power Sockets)

Line 1
Line 0
ETERNUS AF
Drive enclosure
Controller
enclosure
Line 0
Only connect the ETERNUS AF to circuit protectors.
Power distribution unit
ETERNUS AF
PSU
PSU
FUJITSU Storage ETERNUS AF250 S2, ETERNUS AF250 All-Flash Arrays Site Planning Guide
Copyright 2021 FUJITSU LIMITED
CP
Line 1
28
P3AG-1812-06ENZ0