Technical specifications
Article number
General information
Firmware version
Usable terminal block
Color code for module-specific color identifica‐
tion plate
Engineering with
Operating mode
Redundancy
Supply voltage
Rated value (DC)
permissible range, lower limit (DC)
permissible range, upper limit (DC)
Reverse polarity protection
Input current
Current consumption (rated value)
Current consumption, max.
Power loss
Power loss, typ.
Address area
Address space per module
Digital outputs
Short-circuit protection
Open-circuit detection
Overload protection
Limitation of inductive shutdown voltage to
Controlling a digital input
Switching capacity of the outputs
32
FW update possible
SPPA-T3000 can be configured/integrated
from version
DQ
DQ with energy-saving function
Redundancy capability
Address space per module, max.
Response threshold, typ.
with resistive load, max.
6DL1132-6BH00-0EH1
V1.0
Yes
TB type H1 and M1
CC02
V8.0
Yes
No
Yes; With TB type M1
24 V
19.2 V
28.8 V
Yes
60 mA; without load
70 mA; without load
1.2 W; minimum - typ. specification not possible
because load-dependent
8 byte; PII: 0 bytes, +2 bytes for QI information, +2
bytes of PROFINET status data; PIO: 2 bytes, +2
bytes of PROFINET status data
Yes; Ensure sufficient low-resistance cable routing
to the sensor/actuator in order to attain the re‐
sponse threshold. Depending on the cable cross-
section used, there may be constraints regarding
the usable length of cable.
0.7 A to 1.3 A (for IO redundancy up to max 2.6 A)
Yes; 0.7 mA test current for wire-break diagnostics;
this value is doubled in the case of IO redundancy
Yes
L+ -(37 to 41V)
Yes
0.5 A
Equipment Manual, 10/2021, A5E39265993-AD