Article number
•
Load resistance range
•
•
Output current
•
Output delay with resistive load
•
•
Parallel switching of two outputs
•
•
Switching frequency
•
•
Total current of the outputs
•
Total current of the outputs (per module)
horizontal installation
vertical installation
Cable length
•
•
Interrupts/diagnostics/status information
Diagnoses
•
•
•
•
•
Diagnostics indication LED
•
DQ 16x24VDC/0.5A
Equipment Manual, 10/2021, A5E39265993-AD
on lamp load, max.
lower limit
upper limit
for signal "0" residual current, max.
"0" to "1", typ.
"1" to "0", typ.
for uprating
for redundant control of a load
with inductive load, max.
on lamp load, max.
Current per channel, max.
– up to 30 °C, max.
– up to 40 °C, max.
– up to 50 °C, max.
– up to 60 °C, max.
– up to 70 °C, max.
– up to 30 °C, max.
– up to 40 °C, max.
– up to 50 °C, max.
– up to 60 °C, max.
shielded, max.
unshielded, max.
Monitoring the supply voltage
Wire-break
Short-circuit to M
Short-circuit to L+
Group error
MAINT LED
Technical specifications
6DL1132-6BH00-0EH1
5 W
48 Ω
12 kΩ
0.7 mA; Test current for wire-break diagnostics; this
value is doubled in the case of IO redundancy
50 µs
100 µs
No
Yes
2 Hz
10 Hz
0.5 A
8 A
8 A
8 A
5.5 A
3 A
8 A
6.33 A
4.67 A
3 A
1 000 m
600 m
Yes
Yes; channel by channel
Yes; channel by channel
Yes; channel by channel
Yes
Yes; Yellow LED