670/650 series and SAM600-IO IEC
Injection equipment
Rule: If injection equipment is ordered, ROTIPHIZ or STTIPHIZ is required in the IED.
Injection unit, REX060
The REX060 injection unit requires a connection to a VT across the generator neutral
point earthing resistor. The VT must have a rating of at least 100 VA and a rated
secondary winding voltage of up to 120 V. It must adhere to IEC 61869-3:2011 section
5.5.301 Rated Output Values and the standard values specified according to burden
range II.
Casing
1/2 x 19" rack casing
Backplane module (BPM)
Human machine interface
HMI and logic module (HLM)
Injection modules
Note: One of RIM and SIM have to be selected if REX060 is specified
Rule: Stator injection module (SIM) is required if 100% stator earth fault protection,
injection based (STTIPHIZ) is selected/active in REG670
Stator injection module (SIM)
If the generator is earthed via a primary resistor connected between the generator neutral
point and earth, a VT is placed across the primary resistor. SIM is then connected to the
secondary side of the VT. The VT must have a rating of at least 100 VA and a rated
secondary winding voltage of up to 120 V. It must adhere to IEC 61869-3:2011 section
5.5.301 Rated Output Values and the standard values specified according to burden
range II.
Rule: Rotor injection module (RIM) is required if Sensitive rotor earth fault protection,
injection based (ROTIPHIZ) is selected/active in REG670
Rotor injection module (RIM)
Power supply module
Rule: One Power supply module must be specified
Power supply module (PSM)
Mounting details with IP40 of protection from the front
19" rack mounting kit
Wall mounting kit for terminal
Flush mounting kit for terminal
Extra IP54 mounting seal + flush mounting kit for terminal
Rule: REX061 requires REX060 and that Rotor injection module (RIM) is selected in REX060
and that Sensitive rotor earth fault protection, injection based (ROTIPHIZ) is selected/active in
REG670.
Coupling capacitor unit, REX061
Rule: REX062 requires REX060 and that Stator injection module (SIM) is selected in REX060
and that 100% stator earth fault protection, injection based (STTIPHIZ) is selected/active in
REG670.
Shunt resistor unit, REX062
Hitachi Power Grids
© 2017 - 2021 Hitachi Power Grids. All rights reserved.
1MRK 514 012-BEN K
GUID-3447C871-562C-46B4-A36C-0B8B62D38E48 v8
Quantity:
1MRK 002 500-AA
1MRK 002 544-AA
1MRK 002 544-BA
24-60 VDC
1MRK 002 239-AB
100-250 VDC
1MRK 002 239-BB
1MRK 002 420-BB
1MRK 002 420-DA
1MRK 002 420-EA
Quantity:
1MRK 002 550-AA
Quantity:
1MRK 002 555-AA
Basic
Basic
Basic
1MRK 000 020-Y
29