SUN2000-(250KTL, 280KTL, 300KTL, 330KTL) Series
User Manual
Figure 5-18 Connecting DC input power cables
During DC input power cabling, leave at least 50 mm of slack. The axial tension
on PV connectors must not exceed 80 N. Radial stress or torque must not be
generated on PV connectors.
----End
5.6 Installing Communications Cables
Precautions
When routing communications cables, separate communications cables from
power cables to prevent communication from being affected.
Issue 02 (2022-12-20)
NO TICE
Copyright © Huawei Technologies Co., Ltd.
5 Installing Cables
56