Installation

Line Communication Connection

Multi drop communication using internal DPSK can be performed between IRRInet-M units.
Connect a two-wire cable (not supplied) to the Line Comm connector in the IRRInet-M (see
Figure 15.)
Figure 15 IRRInet-M Line Communication Connection
In a wire line system, the installer must pay close attention to the following
material and installation details:
24
The direct burial cable should meet or exceed the requirements of
a #14-2 underground feeder (UF) cable, with solid copper
conductors.
Burial of the cable must be no less than 30" below finished grade.
The cable shell is only spliced in the field unit enclosure. Where
splices between field units are necessary, an aboveground
weather-tight junction box should be used.