Appendix C: Specifications; Specifications; Environmental; Mechanical - Motorola IRRInet-M DC Owner's Manual

Remote terminal unit
Table of Contents

Advertisement

APPENDIX C: SPECIFICATIONS

Specifications

Environmental

Operating Temperature
Storage Temperature
Relative Operating Humidity
Operating Altitude

Mechanical

Dimensions
Weight
User Connection
Wire Gauge

Basic Board

INPUTS
Number of Inputs
Dry Contact Inputs Ratings
Number of Terminals
Input Isolation
DI Counter
Dry Input
Min Recognizable Pulse Width 20mSec
OUTPUTS (DC Solenoids)
Number of Outputs
Output Drive Voltage
Output Short Circuit Indication > 10A
Single Capacitor
Number of Terminals
Isolation
-30 °C to +60 °C
-55 °C to +85 °C
0 to 95% without condensation @ +50 °C
-400 m to +4000 m above sea level
21.50 x 17.50 x 8.50 cm (max.)
1.50 kg (max.)
4*10 Terminal Blocks (including I/O Expansion)
14 #AWG (2.5 mm square)
4
Open: > 50 kΩ (OFF)
Closed: 0-4 kΩ (ON)
5: 4 DI, DI_COM
1500 VAC between user connector and logic
DI counter capability supported: Input #4
Input Signal Level = Low (Led ON) if < 4.0 k
Input Signal Level = High (Led OFF) if > 50.0 k
DIs do not operate when I/O power supply is OFF.
12
4-35V DC ± 10%
(STS Adjustable ± 1V)
3300 μF
14: SOL_1 – SOL_6, COM1, SOL_7 – SOL_12,
COM2
1500 VAC between user connector and logic
Ω
Ω
41