5.3.5
Input Voltage Tolerances
Table 5.6 lists the input voltage tolerances for the single-phase 9900 subsystem. Transient
voltage conditions must not exceed +15-18% of nominal and must return to a steady-state
tolerance of between +6 and -8% of the normal related voltage in 0.5 seconds or less. Line-
to-line imbalance voltage must not exceed 2.5%. Nonoperating harmonic contents must not
exceed 5%.
Table 5.6
Input Voltage Specifications for Single-Phase Power
Frequency
60 Hz ±0.5 Hz
50 Hz ±0.5 Hz
Note: User input requires a 20-amp circuit breaker for single-phase power.
92
Chapter 5 Planning for Installation and Operation
Input Voltages (AC)
Wiring
200V, 208V or 230V
Single-phase two wire + ground
200V, 220V, 230V or 240V
Single-phase two wire + ground
Tolerance(%)
+6% or -8%
+6% or -8%