Dell 100 Series Hardware Installation Manual page 14

Hide thumbs Also See for 100 Series:
Table of Contents

Advertisement

Before You Begin
VxRack Node Hardware Installation Guide
14
Table 2 Hardware acclimation times (systems and components) (continued)
If the last 24 hours of the
TRANSIT/STORAGE
environment was this:
Nominal 68-72°F
Nominal
(20-22°C)
40-55% RH
Cold <68°F
Dry <30%
(20°C)
RH
Cold <68°F
Damp ≥30%
(20°C)
RH
Hot >72°F
Dry <30%
(22°C)
RH
Hot >72°F
Humid
(22°C)
30-45% RH
Humid
45-60% RH
Humid
≥60% RH
Unknown
NOTICE
If there are signs of condensation after the recommended acclimation time has
l
passed, allow an additional eight (8) hours to stabilize.
Systems and components must not experience changes in temperature and
l
humidity that are likely to cause condensation to form on or in that system or
component. Do not exceed the shipping and storage temperature gradient of
45°F/hr (25°C/hr).
...and the OPERATING
environment is this:
Nominal 68-72°F (20-22°C)
40-55% RH
<86°F (30°C)
<86°F (30°C)
<86°F (30°C)
<86°F (30°C)
<86°F (30°C)
<86°F (30°C)
<86°F (30°C)
...then let the system
or component
acclimate in the new
environment this many
hours:
0-1 hour
4 hours
4 hours
4 hours
4 hours
8 hours
16 hours
16 hours

Advertisement

Table of Contents
loading

Table of Contents