Example: Interpretation of the displayed value of the "Error History":
XML-Ex-/Import
The configuration generated in the OPCUAEdit tool can be exported as an XML file in the
IoT Gateway web server.
This generated XML file can then be edited in any text editor and then transferred back to
the IoT Gateway using "Load XML".
Sample XML file
:
<?xml version="1.0" encoding="UTF-8"?>
<Objects Version="1">
<Device name="INV_01" URL="192.168.0.2:5012">
<CPU name="FU_01" network="0" pcno="255" moduleio="1023" moduleno="0" hexio="1">
<GlobalVars>
<struct name="VarList">
<Variable name="InverterStatus" address="SD1151" type="Int16"/>
<Variable name="OutputFrequencyMonitor" address="SD1133" type="Int16"/>
<Variable name="OutputCurrentMonitor" address="SD1134" type="Int16"/>
<Variable name="OutputVoltageMonitor" address="SD1135" type="Int16"/>
<Variable name="InputPower" address="SD1160" type="Int16"/>
<Variable name="OutputPower" address="SD1161" type="Int16"/>
<Variable name="RunningSpeed" address="SD1153" type="Int16"/>
<Variable name="MotorTorque" address="SD1154" type="Int16"/>
<Variable name="ErrorHistory_01" address="SD1136" type="Int16"/>
<Variable name="ErrorHistory_02" address="SD1137" type="Int16"/>
<Variable name="ErrorHistory_03" address="SD1138" type="Int16"/>
<Variable name="ErrorHistory_04" address="SD1139" type="Int16"/>
</struct>
</GlobalVars>
</CPU>
</Device>
</Objects>
_________________________________________________________________________
Document: Quickstart_IoTGateway_EN
Rev: 001G
Date: 01/02/2022
Mitsubishi Electric Europe B.V.
33