Mn Alarm Indicator; Inputs; 1: Monitor Module And Initiating Device - Honeywell Notifier NFS2-3030 FACP Programming And Operations Manual

Mass notification system
Hide thumbs Also See for Notifier NFS2-3030 FACP:
Table of Contents

Advertisement

MN Alarm Indicator

2.4 MN Alarm Indicator
One of the following must be programmed as a dedicated MN alarm indicator for the NFS-320/SYS, NFS2-640, NFS2-3030, and NCA-
2. The indicator is not required if a panel is acting as a displayless node.
An ACM-24AT or AEM-24AT LED annunciator point.
A DVC-KD point.
An ONYXWorks workstation does not require an additional annunciator point, as it has a dedicated icon to indicate when an MN alarm
is active. This icon is displayed constantly during an MN alarm.
NFS2-640 or NFS-
320/SYS
NCA-2 or NFS2-3030

2.5 Inputs

2.5.1 Monitor Module and Initiating Device
An FMM-1 Monitor Module, FMM-101 Mini Monitor Module, FDM-1
Dual Monitor Module, or XP10-M Monitor Module can be installed to
monitor a UL-approved switch or button device installed for initiating
MN alarms. A Listed UL2017 initiating switch/device is required. It will
generate an MN alarm, MN supervisory, or MN trouble message when it
is programmed with an MN/ECS type code. (Refer to "Type IDs" on
page 24).
Mass Notification — P/N LS10063-000NF-E:E 06/26/2019
Figure 2.4 NFS2-640 or NFS-320/SYS MN Alarm Annunciation
OTHER EVENT
LED for MN alarm
annunciation
Required LED annunciator
or DVC-KD point
programmed to illuminate
when an MN alarm
activates.
Figure 2.5 NFS2-3030, or NCA-2 MN Alarm Annunciation
LED annunciator point
programmed to
illuminate when an MN
alarm activates.
Refer to Section 3.3.11 on
page 34 for programming.
Refer to Section 3.3.11 on
page 34 for programming.
_
+
_
+
Optional
Class A
UL 2017 Listed
manual input
device
Figure 2.6 Monitor Module and Input Device
Configurations
SL
_
+
_
SL
+
Monitor module
13