2: Mass Notification Control Settings For The Dvc; 3: Set The Priority - Honeywell Notifier NFS2-3030 FACP Programming And Operations Manual

Mass notification system
Hide thumbs Also See for Notifier NFS2-3030 FACP:
Table of Contents

Advertisement

Programming
VeriFire Tools: Leave the Display and Control Center box unchecked
in the NFS2-640 and NFS-320/SYS service.
3.3.2 Mass Notification Control Settings for the DVC
Open the General Settings branch of the DVC System Programming Service in VeriFire Tools.
In the General Settings 3 column, set the MN Mode to LOC, ACU, or CCS. The Associated Node Number becomes available in the
Mass Notification Control Settings section.
Enter the node number of the NCA-2 or NFS2-3030 that is associated with the DVC. VeriFire Tools will set this to 0 (zero) if the DVC is
acting as a subsidiary device (i.e., it is not part of an ACU, LOC or CCS).
3.3.3 Set the Priority
NOTE: Program all panels, DVCs, network annunciators and workstations in a system with the same priority settings. The established
priorities must be consistent throughout a system.
DVC will use the priority of the node with which it is associated.
NFS2-3030/NCA-2
This field allows the programmer to define the panel's relative fire and MN priority. The priority may be set at the panel (See Figure 3.6)
or in VeriFire Tools. (See Figure 3.7).
Mass Notification — P/N LS10063-000NF-E:E 06/26/2019
Leave
unchecked.
DVC General Settings Branch,
"General Settings 2" and "General Settings 3" columns
Enter node # of associated NCA-2 or NFS2-3030. If the DVC is acting as a
subsidiary device, 0 (zero) will be entered automatically.
Figure 3.5 DVC MN Mode Setting
NFS2-640/NFS-320/SYS General Settings
Branch, "General Settings 2" column
Figure 3.4 VeriFire Tools, NFS2-640/NFS-320/SYS
Programming
19