2: Microphone Activations For Mn; 3: Acs And Dvc-Kd Activations; Outputs; 1: Strobes And Horns - Honeywell Notifier NFS2-3030 FACP Programming And Operations Manual

Mass notification system
Hide thumbs Also See for Notifier NFS2-3030 FACP:
Table of Contents

Advertisement

Configurations
2.5.2 Microphone Activations for MN
MN Microphone activations are initiated at ACU, LOC and CCS stations. Programming determines which button is assigned to mass
notification.
ACU, LOC, and Non-ONYXWorks CCS Activations
MN ALL CALL paging is activated by pressing one of the top two paging buttons in the second column of DVC-KD buttons, then using
the microphone to page. Programming determines which button it is. MN paging will be the top button if MN is programmed as the
highest priority in the system. It will be the second paging button down if Fire is programmed as the highest priority in the system. (Fire
paging will be the top button.) MN paging activates an MN alarm.
ONYXWorks Activations
MN paging is activated by clicking the audio button for the desired MN paging group. MN paging groups are listed on the right side of
the workstation graphic area. The Live Microphone dialog box will open and the Start Paging bar will be available to click and use the
microphone to page.
2.5.3 ACS and DVC-KD Activations
Annunciator buttons, and the buttons in the two right columns of a DVC-KD, can be programmed to initiate MN alarms for vectored
paging or for playing pre-recorded MN messages. Refer to "Programming" on page 15, and to the DVC manual for more information.

2.6 Outputs

2.6.1 Strobes and Horns
Notification Appliance Circuits (NACs) for driving strobes and horns can be shared between fire and mass notification, or they can be
dedicated to a single application. When dedicated, releasing zone operation will not be affected by the state of MN in the system. For fire
and MN, only the highest priority active event will cause activations.
Strobe circuits that are associated with MN or an MN/Fire combination must be programmed as non-silenceable.
2.6.2 Speakers
All speakers on a DAL (Digital Audio Loop) will play live and pre-recorded MN messages according to their programming. They can be
shared between fire, mass notification, and releasing applications.
2.6.3 CAP Gateway
The CAP Gateway is a primary output for an MN System.

2.7 Supplemental Equipment

The following equipment is listed for UL2572 supplemental use.