Commissioning
Operating hours value range
This parameter serves as a note or remark.
The value range is between 0 and 100,000.
Count operating hours with switch position
Options:
ON/
OFF/
ON and OFF (always)
With this parameter you set the switch state at which the operating hours are
to be counted.
Option ON = counting is undertaken at a communication object value of "1",
i.e. at a communication object value of "1" the operating hours counter is
started and the counting stops at a value of "0".
Option OFF = counting is undertaken at a communication object value of "0",
i.e. at a communication object value of "0" the operating hours counter is
started and the counting stops at a value of "1".
Option ON and OFF (always) = counting is undertaken at a communication
object value of "0" and "1". After the Data Logging Unit is powered up the
operating hours counter will run permanently.
Thus for example the total connection time of equipment in the
®
ABB i-bus
system can be measured.
Note:
Internally the Data Logging Unit counts exactly to the second,
the output of the operating hours telegram occurs for example
at a full 60 minutes, 120 minutes etc.
Count operating hours with connection failure to channel
Options:
Count/
Do not count/
Dependent on last switch position
Option Count = the operating hours continue to count.
Option Do not count = the operating hours are not counted, i.e. as soon as
the connection to the channel has been established the count will continue.
Option Dependent on last switch position = depending on the last
communication object value the count will or will not continue.
21