ABB i-bus BDB/S 1.1 Product Manual page 23

Eib / knx data logging unit
Table of Contents

Advertisement

®
ABB i-bus
EIB / KNX
© 2006 ABB STOTZ-KONTAKT GmbH
Commissioning
Operating hours count method
Options:
Total runtime/Remaining runtime
Option Total runtime = counting upwards (incremental counter) beginning
at 0.
Option Remaining runtime = counting downwards (decremental counter)
beginning at the start value.
Note:
All details in hours.
If the option Total runtime is selected, the following two parameters are
displayed.
Operating hours limit value
Options:
0...1000...100,000
The limit value for the operating hours is set with this parameter. If this value
is reached the communication object "Channel 1 operating hours - Alarm"
sends a "1".
Note:
Thereafter counting will continue up to the end value of
100,000. The counter value stops at 100,000.
Overwrite operating hours limit value with download
Options:
no/yes
Option no = operating hours limit value is not overwritten
Option yes = operating hours limit value is overwritten
Note:
Changes of the limit value via the bus with a download is not
taken into consideration. The parameterised value is set as
a limit value.
If the option Remaining runtime is selected, the following two parameters
are displayed.
Operating hours start value
Options:
0...1000...100,000
The start value for the operating hours is set with this parameter. Counting
down to zero starts at the start value. If the value "0" is reached the
communication object "Channel 1 operating hours - Alarm" sends a "1".
Note:
The counter stops at zero.
Overwrite operating hours start value with download
Options:
no/yes
Option no = operating hours start value is not overwritten
Option yes = operating hours start value is overwritten
Note:
Changes of the start value via the bus with a download is not
taken into consideration. The parameterised value is set as a
start value.
23