6.
Apply input signal(s), for start of CCRBRF.
7.
Arrange disconnection of CB closed signal(s) well before set back-up trip time t2.
8.
Verify that back-up trip is not achieved.
10.4.6.10
Verifying the caseFunctionMode = Current or CB Pos
To be made only whenFunctionMode = Current or CB Pos is selected. It is suggested to make the
tests in one phase only, or at three-phase trip applications for just three-phase tripping.
Checking the case with fault current above set value IP>
The operation shall be as in RetripMode = UseFunctionMode.
1.
Set FunctionMode = Current or CB Pos.
2.
Leave the inputs for CB close inactivated. These signals should not influence.
3.
Apply the fault condition, including the start of CCRBRF, with the current above the set IP>
value.
4.
Check that the re-trip, if selected, and back-up trip commands are achieved.
Checking the case with fault current below set value I>BlkCBPos
The case shall simulate a case where the fault current is very low and operation will depend on CB
position signal from CB auxiliary contact. It is suggested that retrip without current check is used,
setting RetripMode = UseFunctionMode Check.
1.
Set FunctionMode = Current or CB Pos.
2.
Apply input signal for CB closed to the relevant input or inputs CBCLDL1 (2 or 3).
3.
Apply the fault condition with input signal(s) for start of CCRBRF. The value of current should
be below the set value I>BlkCBPos.
4.
Verify that phase selection re-trip (if selected) and back-up trip are achieved after set times.
Failure to trip is simulated by keeping the signal(s) CB closed activated.
5.
Disconnect the input signal and the START signal(s). Keep the CB closed signal(s).
6.
Apply the fault and the start again. The value of current should be below the set value
I>BlkCBPos.
7.
Arrange disconnection of CB closed signal(s) well before set back-up trip time t2. It simulates a
correct CB tripping.
8.
Verify that back-up trip is not achieved. Re-trip can appear for example, due to selection
RetripMode = Always.
10.4.6.11
Verifying the external start signal has timed out
1.
Set StartMode = FollowStart.
2.
Set FunctionMode = Current.
3.
Use default value for tStartTimeout = 1.0 s.
4.
Use default value for time delay backup trip t2 = 0.150 s.
5.
Leave the inputs for CB close inactivated. These signals should not influence.
6.
Apply START signal, and after 1.5 s apply the current above the set IPh> value.
7.
Check that STALARM signal is set after 1.0 s and backup trip is blocked.
10.4.6.12
Verifying that backup signal is released when STALARM is reset
1.
Set StartMode = FollowStart.
2.
Set FunctionMode = Current.
3.
Use default value for tStartTimeout = 1.0 s.
4.
Use default value for time delay backup trip t2 = 0.150 s.
5.
Leave the inputs for CB close inactivated. These signals should not influence.
6.
Apply START signal at t=0s, and after 1.5 s apply the current above the set IPh> value.
Busbar protection REB670
Commissioning manual
© 2017 - 2022 Hitachi Energy. All rights reserved
Section 10
Testing functionality by secondary injection
M12104-281 v11
GUID-754108D4-E440-4F8F-917B-04579EC1C2C7 v1
GUID-49CA34B6-5AE9-4E45-9F4E-33DA5F626209 v1
M12104-237 v7
M12104-241 v8
87