Fujitsu AIRSTAGE UTY-ABGXZ1 Instruction Manual page 40

Gateway for vrf system
Table of Contents

Advertisement

When "Omit Login screen at startup" is checked, the password screen is omitted at application starting
from the next time.
At the end of an application, at DB importing, etc. the password input screen is displayed the same as
up to now.
Click the "OK" button
Items
"IP Address"
"Subnet Mask"
"Device Instance No."
"Device Object Name"
"Max_APDU_Length_Accepted"
"APDU_Timeout (m sec)"
"Number_of_APDU_Retries"
"APDU_Segment_Timeout (m sec)"
"Set the same value to TIime_Delay_Normal
when writing to the Time_Delay"
"I-Am Service Broadcast Sending
(at 60-second intervals)"
"Unconfirmed COV Notification Service
Broadcast Sending"
"Process ID"
"Synch. VRF System Time to Time Synchro-
nization/UTCT Time Synchronization."
"Register as Foreign Device with BBMD"
"BBMD at IP Address"
"BBMD at UDP Socket"
"Temperature Units"
*1
"Capacity Units"
"Omit Login screen at startup"
Copyright© 2010-2017 Fujitsu General Limited. All rights reserved.
Contents
Enter the IP address used in BACnet
Enter the subnet mask corresponding to the IP address used in
®
BACnet
communications.
Enter the Instance No. of the local Device.
Enter the object name of the local Device. (Up to 50 ASCII charac-
ters)
Select the acceptable APDU length.
Enter the APDU timeout time in milliseconds.
Select the number of retries when time out occurs.
Enter the internal time at which APDU segment is resent, in milli-
seconds.
When writing into "Time-Delay-Normal" cannot be performed, place
a check mark in this option.
The value is stored when writing into "Time_Delay_Normal" even if
a check mark is in place.
Check when you want to send I-Am Service periodically. (60-second
intervals)
COV notification is sent by broadcast even when SubscribeCOV
service is not subscribed. Refer to the interface specifications for
the target object.
* Depending on the number of units and their status,large number
of packets are sent.
Process ID used when sending COV notification.
Check if you want to send "system time setting" to VRF units when
TimeSynchronization/UTCTimeSynchronization Service is received.
Check when you register as an external device to BBMD.
BBMD IP address.
BBMD UDP port No.
"Celsius" or "Fahrenheit" can be selected. Select the units to be
used at temperature display.
"BTU" or "kW" can be selected. The selected unit will be used for
displaying the capacity values in the main screen.
When "Omit Login screen at startup" is checked, the password
screen is omitted at application starting from the next time.
At the end of an application, at DB importing, etc. the password
input screen is displayed the same as up to now.
40
®