6. Vendor Specification Profile

Cyclic transmission of command and monitor is possible for this product by the original profile
Select the "Telegram 100", "Telegram 101" or "Telegram 102" as the profile on the configuration. Refer
to the document of network configuration tool of the PROFINET controller (PLC).
You will be able to select the command and monitor items from the following table.
Please execute these settings by the network configuration tool of the PROFINET controller (PLC).
When you use "Telegram 100","Telegarm101" or "Telegarm102", the value is written to the RAM.
VF-S15/MB1 profile
Scanner input c001 - c006
0: No action
1:
(Communication command 1)
fa06
2:
(Communication command 2)
fa23
3:
(Frequency command, 0.01Hz)
fa07
5:
(Terminal output data)
fa50
6:
(FM analog output)
fa51
8:
(Stall prevention level, %)
f601
13:
(Acceleration time 1, 0.1s)*
acc
14:
(Deceleration time 1, 0.1s) *
dec
15:
(Upper limit,0.01Hz)
ul
16:
(Torque boost value 1,0.1%)
vb
17:
(Base frequency voltage 1, 0.1V)
vlv
* The unit of
,
acc
dec
** The unit of
,
fe76
Notes
is according to the parameter
is according to the parameter
fe77
Scanner output c021 - c026
0: No action
1:
(Status information 1)
fd01
2:
(Output frequency, 0.01Hz)
fd00
3:
(Output current, 0.01%)
fd03
4:
(Output voltage, 0.01%)
fd05
5:
(Alarm information)
fc91
6:
(PID feedback value, 0.01Hz)
fd22
7:
(Input terminal status)
fd06
8:
(Output terminal status)
fd07
9:
(VIB input, 0.01%)
fe36
10:
(VIA input, 0.01%)
fe35
11:
(VIC input, 0.01%)
fe37
12:
(Input voltage (DC detection), 0.01%)
fd04
13:
(Estimated speed (real-time value), 0.01Hz)
fd16
14:
(Torque, 0.01%)
fd18
19:
(Free notes)
f880
20:
(Input power, 0.01kW)
fd29
21:
(Output power, 0.01kW)
fd30
22:
(Cumulative operation time, 1hour)
fe14
23:
(FM terminal output monitor, 0.01%)
fe40
25:
(Torque current, 0.01%)
fd20
26:
(Motor overload factor, 0.01%)
fd23
27:
(Drive overload factor, 0.01%)
fd24
28:
(PBR overload factor, %)
fd25
29:
(Motor load factor, %)
fd26
30:
(Drive load factor, %)
fd27
31:
(Pulse train input, pps)
fe56
32:
(Drive rated current, 0.1A)
fe70
33:
(Input Watt-hour, 0.1kWh  10
fe76
34:
(Output Watt-hour, 0.1kWh  10
fe77
35:
(IGBT temperature, degree C)
fd83
.
f519
.
f749
- 33 -