Switch operation process: After turning on the grounding switch of the outgoing cable cabinet
at the booster station, take out the key to the grounding switch of cabinet G1. After the key is
returned, you can turn off the grounding switch of the outgoing cable cabinet.
Procedure
Step 1 Mechanical lock K1 is configured at the operation hole of the grounding switch in cabinet G1.
After the K1 key is inserted, you can turn on or off the grounding switch. You can remove the
K1 key only after the grounding switch is turned off.
Step 2 Mechanical lock (not a padlock) K2 is configured at the operation hole of the grounding
switch in cabinet G3. After the K2 key is inserted, you can turn on or off the grounding switch.
You can remove the K2 key only after the grounding switch is turned on.
Step 3 Based on the hand-in-hand connection diagram of the STSs obtained from the customer, put
the K2 key of cabinet G3 in STS 1 and the K1 key of cabinet G1 in STS 2 on the same key
ring. Mark the STS and switch numbers on the labels. The operations for STS 2 and STS 3 are
similar. Turn on the grounding switch of cabinet G3 in the last STS. Remove the K2 key and
hand it over to the O&M personnel.
Step 4 For the first STS closest to the booster station, the key to the grounding switch of cabinet G1
needs to be interlocked with the outgoing cable knife switch of the booster station. The
interlocking logic is the same as that of STSs. If the knife switch does not have the
interlocking function, interlocking can be performed with the disconnector. The operation
hole of the disconnector should be equipped with a mechanical lock (not a padlock). After the
key is inserted, the disconnector can be turned on and off. The key can be removed only after
the disconnector is turned off.
Step 5 If the disconnector and the grounding switch do not have the interlocking function, turn off
the grounding switch of cabinet G1 and remove the key. Then hand the key over to the O&M
personnel for proper storage. According to the requirements, interlock the grounding switch
of the booster station with that of the first STS to ensure operation safety.
Figure 5-5 Interlocking between STSs with a CVC ring main unit
----End
Issue 02 (2020-02-21)
Copyright © Huawei Technologies Co., Ltd.
5 Operating Components
35