Step 4. Final Assembly; Figure 10 Fuse Blocks; Figure 11 Clear Removable Panel; Figure 12 Cabinet Grounding - ABB G391 Series Quick Start Manual

Edge ac short circuit current limiter
Table of Contents

Advertisement

QUICK START GUIDE

Step 4. Final Assembly

1.
Verify all fuses are fully assembled into each
position of the fuse blocks.
2. Attach clear, removable panel to the top cover.
Torque to 10in-lb.
3. Connect ground wire provided in the G391 kit to
the ground lug located on the bottom of the
base panel assembly. Connect the other end of
the ground wire to the cabinet ground bus.
Torque lug set screw to 45in-lb.
Torque screw on ground bus to 65in-lb.
Note: 2-hole compression lugs are also provided
which can be used instead of the single-hole
mechanical lug.
Page 11
© 2023 ABB. All rights reserved.
Edge_Ilim_G391_QSG

Figure 10 Fuse blocks

Figure 11 clear removable panel

Figure 12 Cabinet grounding

Ground wire
Version. 2.0