Indoor Unit - Electric Control Sys
tem
Semiannual Maintenance (2)
Inspection
No.
Method
Use a brush or compressed dry air to clean various
Visual
electric components, control components, the main
5
inspection
control board, and the surge protection and voltage test
board.
Check that the main control board, display panel,
Visual
temperature and humidity sensor, surge protection and
6
inspection
voltage test board, and power cables are free from
aging on the surface.
Check that the transformer is intact and the
Visual
7
output voltage is within the normal range (24 V AC ±
inspection
10%).
Visual
Check that all circuit breakers are working
8
inspection
properly.
Copyright © 2017 Huawei Technologies Co., Ltd. All rights reserved.
Operations
Troubleshooting
N/A
Replace the
components
or cables.
Check whether the
power input cable is
properly. If
no, reconnect it. If
yes, replace the
transformer.
Replace the circuit
breakers.
Page 17