Replacing Water Supply Valve (2)
( 1 ) Nut of the
water inlet pipe
( 3 ) Water supply
valve
Copyright © 2017 Huawei Technologies Co., Ltd. All rights reserved.
( 2 ) Connection nut
Step 3 Fix the connective nut shown by 2
in Figure using an adjustable wrench, and
loosen the nuts at both ends (as shown by
1 in Figure) using an adjustable wrench.
Then remove the water injection solenoid
valve;
Step 4 Perform Step 2 to Step 3 in
reverse order to reinstall the new water
supply valve.
Step 5 Power on the equipment. On the
main screen, choose Maint >
Diagnostic Mode > Enter, on the main
menu, open the water supply valve and
humidif er, and check that the humidif er
works properly. Then exit from the
diagnostic mode.