Intelligent mode selection (Pr. 60)

Pr. 60 "intelligent mode selection"
The inverter automatically sets appropriate parameters for operation.
If you do not set the acceleration and deceleration times and V/F pattern, you can run the inverter as if
z
appropriate values had been set in the corresponding parameters. This operation mode is useful to start
operation immediately without making fine parameter settings.
Parameter
Factory Setting
Number
60
<Setting>
Pr. 60
Operation Mode
Setting
Ordinary operation
0
mode
Shortest
1, 2
acceleration/
deceleration mode
Optimum
acceleration/
3
deceleration mode
(Note 2, 4)
Energy-saving
4
mode (Note 3, 5)
Elevator mode
5, 6
(Note 3)
7
Brake sequence
mode
8
Setting Range
0
0 to 8
Set to accelerate/decelerate the motor in the shortest time. The
inverter makes acceleration/deceleration in the shortest time using its full
capabilities. During deceleration, an insufficient brake capability may cause
the regenerative overvoltage alarm (E.OV3).
"1": Stall prevention operation level 150%
"2": Stall prevention operation level 180%
Optimum operation can be carried out by fully utilizing the inverter
capabilities in the continuous rating range.
Self-learning automatically sets the corresponding parameters so that the
average current during acceleration/deceleration is equal to the rated current.
Appropriate for applications where the load will not vary by a large ammount.
Tunes the inverter output voltage online to minimize the inverter
output voltage during constant-speed operation.
Appropriate for energy-saving applications such as fan and pump.
Automatically controls the inverter output voltage to deliver the
maximum torque in both the driving and regenerative modes. Appropriate
for a counterbalanced elevator.
"5": Stall prevention operation level 150%
"6": Stall prevention operation level 180%
Mechanical
brake opening
This function causes the inverter to output the
completion signal
mechanical brake operation timing signal for elevating
input
application.
Mechanical
For function details and related parameter setting, refer
brake opening
to Pr. 278 to Pr. 285 (brake sequence functions).
completion
signal not input
CAUTION
Related parameters
Pr. 0 "torque boost"
Pr. 7 "acceleration time"
Pr. 8 "deceleration time"
Pr. 13 "starting frequency"
Pr. 19 "base frequency voltage"
Pr. 80, Pr. 81
(advanced magnetic flux vector control)
Pr. 278 to Pr. 285
(brake sequence functions)
Description

88
PARAMETERS
Automatically Set
Parameters

Pr. 7, Pr. 8
Pr. 0, Pr. 7, Pr. 8
Output voltage
Pr. 0, Pr. 13, Pr. 19
