Input Testing; Walk Test All Zones; Walk Test A Single Zone; Sensor Watch Time - Bosch Solution 16i Installation Manual

Hide thumbs Also See for Solution 16i:
Table of Contents

Advertisement

Solution 16i
Installation Manual
I N P U T T E S T I N G
Inputs > Input Testing >

Walk Test All Zones

This menu allows you to test all zones within an area at the
same time. To successfully walk test each zone, you must
open and close each zone.
1) Enter your PIN + [MENU].
2) Enter [3] + [9] + [0] + [OK].
The keypad will display a list of all zones to be tested.
If your system is configured for multiple areas then
you may be prompted to select the area to test.
1 2 3 4 5 6 7 8
3) Fault and restore each zone that needs to be tested.
A zone that has been successfully tested will no longer
be displayed on the keypad display.
When all zones have been tested, the keypad will
display PASS.
4) Press [OK] to exit.
Inputs > Input Testing >

Walk Test A Single Zone

This menu allows you to select a single zone to be tested
via walk test.
1) Enter your PIN + [MENU].
2) Enter [3] + [9] + [1] + [OK].
The keypad will display the Zn = prompt.
3) Enter the zone number you want to test, then press
[OK].
2
4) Fault and restore the zone to be tested.
If the zone test was sucessful, the keypad will display
PASS.
7-14
Input Programming
tstzns
-
-
MENU 3-9-0
test
PASS
tst-zn
-
-
MENU 3-9-1
Zn=
test
The system will also chirp the sirens for 1 second if
the zone test was sucsessful making it easier for one
person to do the test.
Inputs > Input Testing >

Sensor Watch Time

(*** System Wide Parameter ***)
This menu programs the Sensor Watch Time interval.
Zones programmed for Sensor Watch are required to seal
and unseal at least once within the Sensor Watch Time
period or a trouble message will be displayed on the
keypad and a Zone Trouble report sent.
Valid entries are 1 -255 Days and 0 = Sensor Watch Disabled
1) Enter your Installer PIN + [MENU].
2) Enter [3] + [9] + [2] + [OK]. The keypad will display
the current sensor watch time (Default = 30 days).
3) Using the numeric keys, enter the new Sensor
Watch time in days then press [OK] to save and exit
or press [MENU] to exit without saving.
Sensor Watch monitoring is only active when the
i
area is in the disarmed state. 24 hour zone types
Note
cannot be monitored using the Sensor Watch feature.
» » E N D
PASS
L392
MENU 3-9-2
0 3 0
d= 030
S E C T I O N « «
O F
Bosch Security Systems 09/11 BLCC500I
DAYS

Advertisement

Table of Contents
loading

Table of Contents