Panasonic PAW-160MAH3M Installation Instructions Manual page 37

Air handling unit kit
Table of Contents

Advertisement

AHU Kit model
Outdoor unit – PACi NX Elite
Nominal cooling capacity
Nominal heating capacity
Piping connections
Liquid pipe
Gas pipe
Piping length
Min / Max
Precharged length (R32)
Max
Additional refrigerant charge (R32) due to extended piping
length
Ambient temperature (outdoor unit)
Cooling (Min / Max) °C DB
Heating (Min / Max) °C WB
AHU unit under "standard conditions"
Air volume flow
Cooling (Min / Max) m³/h
Air intake temperature
Cooling (Min / Max) °C DB
1
Heating (Min / Max) °C DB
AHU DX coil heat exchanger volume Min / Max
Heat exchanger face area
Min / Max
AHU unit under "special conditions A"
2
Air volume flow,
Cooling (Min / Max) m³/h
subject to restrictions
2
Air intake temperature
Cooling (Min / Max) °C DB
1
Heating (Min / Max) °C DB
AHU unit under "special conditions B"
3
AHU DX coil heat exchanger volume,
Min / Max
subject to restrictions
3
Additional refrigerant charge (R32) due to larger heat
exchanger volume
Max. additional refrigerant charge (R32)
Max. pipe length
Max. ambient temp. for pump down
Outdoor unit
PACi NX Standard
U-25PZ3E5
U-36PZ3E5
U-50PZ3E5
U-60PZ3E5
U-71PZ3E5
U100-PZ3E5/8
U125-PZ3E5/8
U140-PZ3E8
PACi NX Elite
U-36PZH3E5
U-50PZH3E5
U-60PZH3E5
U-71PZH4E5/8
U-100PZH4E5/8
U-125PZH4E5/8
U-140PZH4E5/8
Maximum allowed air volume flow under "Standard conditions"
1 Air intake temperature entering the AHU DX coil heat exchanger
2 Special conditions A: Using an AHU unit with a higher maximum allowed air volume flow is subject to a restriction of the
"Air intake temperature" to 30 °C DB (instead of 32 °C WB under standard conditions).
3 Special conditions B: Using an AHU DX coil heat exchanger with a larger volume is subject to the following restrictions:
Note: The AHU DX coil must be designed according to Panasonic specification.
Calculation example for total additional refrigerant charge (R32)
Unit: U-71PZH4E8
Pipe length: 40 metres
AHU DX coil volume (supplied by AHU manufacturer): 2.1 dm³
AHU Kit – Installation Instructions – 07/2023
U-36PZH3E5
kW
3,6
kW
3,6
Inch (mm)
1/4 (6,35)
Inch (mm)
1/2 (12,70)
m
3 / 40
m
30
kg/m
0.015
-15 / +46
-20 / +24
360 / 870
18 / 32
°C WB
14 / 25
16 / 30
dm
1.0 / 1.3
3
m
– / –
2
360 / 900
18 / 32
°C WB
14 / 25
16 / 30
dm
1.0 / 1.5
3
kg/dm
0.83
3
kg
0.17
m
25
°C DB
n/a
an additional refrigerant charge (R32), which is required irrespective of an additional refrigerant charge
which might be needed due to an extended piping length (see calculation example below)
AND a reduced maximum pipe length
AND an ambient air temperature limit above which it may not be possible to pump down the complete
refrigerant charge (including all additional refrigerant) into the outdoor unit.
PAW-280PAH3M-1
U-50PZH3E5
U-60PZH3E5 U-71PZH4E5/8 U-100PZH4E5/8
5
6
7.1
5
6
7.5
1/4 (6,35)
1/4 (6,35)
3/8 (9,52)
1/2 (12,70)
1/2 (12,70)
5/8 (15,88)
3 / 40
3 / 40
5 / 60
30
30
30
0.015
0.015
0.03
-15 / +46
-15 / +46
-15 / +52
-20 / +24
-20 / +24
-20 / +24
510 / 990
780 / 1,320
720 / 1,740
18 / 32
18 / 32
18 / 32
14 / 25
14 / 25
14 / 25
16 / 30
16 / 30
16 / 30
1.0 / 1.3
1.1 / 1.4
0.26 / 0.41
– / –
– / –
– / –
630 / 1,080
780 / 1,600
720 / 1,900
18 / 32
18 / 30
18 / 30
14 / 25
14 / 25
14 / 25
16 / 30
16 / 30
16 / 30
1.0 / 1.5
1.1 / 1.8
1.2 / 2.5
0.83
0.83
0.83
0.17
0.33
0.58
25
18
40
n/a
30
30
Air volume flow m³/h
Higher maximum allowed air volume flow under "Special conditions A
Maximum allowed air intake temperature at AHU DX coil heat exchanger in cooling mode is restriced to 30 °C DB.
Product description
U-125PZH4E5/8
U-140PZH4E5/8
10
12.5
10.8
13.5
3/8 (9,52)
3/8 (9,52)
5/8 (15,88)
5/8 (15,88)
5/8 (15,88)
5 / 100
5 / 100
30
30
0.04 (< 85 m);
0.04 (< 85 m);
0.04 (< 85 m);
0.025 (85 ... 100 m)
0.025 (85 ... 100 m)
0.025 (85 ... 100 m)
-15 / +52
-15 / +52
-20 / +24
-20 / +24
780 / 2,610
960 / 3,480
1,170 / 2,970
18 / 32
18 / 32
14 / 25
14 / 25
16 / 30
16 / 30
1.7 / 2.1
1.7 / 2.1
0.4 / 0.6
0.4 / 0.8
780 / 2,800
960 / 3,600
1,170 / 3,600
18 / 30
18 / 30
14 / 25
14 / 25
16 / 30
16 / 30
1.7 / 3.4
1.7 / 3.4
0.83
0.83
1.08
1.08
75
75
30
30
":
2
14
15.5
3/8 (9,52)
5 / 100
30
-15 / +52
-20 / +24
18 / 32
14 / 25
16 / 30
1.7 / 2.1
0.4 / 0.8
18 / 30
3
14 / 25
16 / 30
1.7 / 3.4
0.83
1.08
75
30
37

Advertisement

Table of Contents
loading

This manual is also suitable for:

Paw-280mah3mPaw-560mah3mPaw-280pah3m-1

Table of Contents