Panasonic PAW-160MAH3M Installation Instructions Manual page 57

Air handling unit kit
Table of Contents

Advertisement

Allocation
Terminal No.
X6
AO1
X6.1
4 – 20 mA Higher potential
l
AO2
X6.2
4 – 20 mA Lower potential
l
l
AI1
X6.3
0 to 10 V DC Higher potential
AI2
X6.4
0 to 10 V DC Lower potential
l
T/D1
X6.5
No polarity
l
l
T/D2
X6.6
No polarity
COM
X6.7
Lower potential for DI1 to DI3
l
Digital Input 1
DI1
X6.8
l
Higher potential
Digital Input 2
l
DI2
X6.9
Higher potential
Digital Input 3
DI3
X6.10
l
Higher potential
COM
X6.11
COM for DO2
l
l
DO2
X6.12
Alarm Signal
COM
X6.13
COM for DO1
l
DO1
X6.14
Operation Signal
l
AHU Kit – Installation Instructions – 07/2023
Function
Analogue output terminals
Analogue input terminals for temperature and demand
control
Activation of demand control
Digital Inputs
(For information on functionality refer to section
"Terminal layout – CZ-CAPBC2 / ACC-SP1A" in this
document or in the dedicated installation instruction of
CZ-CAPBC2)
Alarm Signal
Operation Signal
Electrical Wiring
Description
Analog output (Room temperature monitor), Indoor temperature
monitor output. Output current : 4 to 20 mA. Temperature indica-
tion range : 5 to 36 °C, 0.5 °C step
Analogue input (+10 V DC) for demand control / temperature
control
Analog input Negative potential (–10 V DC) for demand control /
temperature setting
Insert bridge to activate temperature control (system is set for
demand control as standard)
2 types of usage:
a) Potential-free:
Keep S3 of CZ-CAPBC2 / ACC-SP1A on "NON VOLTAGE".
b) 12 to 24 V DC, 10 mA external:
Change S3 of CZ-CAPBC2 / ACC-SP1A to "VOLTAGE".
External Potential: max. 230 V AC / 3 A
External Potential: max. 230 V AC / 3 A
5
57