Pah3 Model - Panasonic PAW-160MAH3M Installation Instructions Manual

Air handling unit kit
Table of Contents

Advertisement

Electrical Wiring
Switch S3: Digital input configuration setting (voltage/non-voltage signals)
Depending on the BMS digital input (DI) configuration, switch S3 on the CZ-CAPBC2 interface can
be set for the digital input terminals to accept either non-voltage signals from dry contacts (factory
default: "NON VOLTAGE") or 12 – 24 V DC signals ("VOLTAGE").
S2
JP6
JP5
i
JP4
Important
JP3
For more details about the connection and functions of the CZ-CAPBC2 interface, please refer to
JP2
the separate installation instructions for CZ-CAPBC2.
JP1

5.3.2 PAH3 model

BOOT MODE
Terminal layout – Main terminal board (ACXA73-38670)
Terminal No.
X1
L
X1.1
l
N
X1.2
l
5
l
3
X1.3
PE
X1.4
l
Terminal No.
X2
l
F1
X2.1
F2
X2.2
l
Terminal No.
X3
FS1
X3.1
l
FS2
X3.2
l
T10.1
X3.3
l
T10.2
X3.4
l
EX1
X3.5
l
EX2
X3.6
l
To be continued on next page.
60
Set S3 to "VOLTAGE",
if digital inputs are to accept
12 – 24 V DC signals
S1
ON
ON
D3
1 2 3 4
1
4
OFF
S5
NORMAL
Allocation
Function
Live
Live Terminal
Neutral
Neutral Terminal
Comm
Communication terminal
Protective earth
Protective Earth Conductor
Allocation
Function
COM for F2
Fan Operation Signal
Fan contact
Allocation
Function
Lower Potential for FS
Float switch
(ex factory bridged)
Higher Potential for FS
Higher Potential for T10
ON/OFF (operation/stop by external signal)
Lower Potential for T10
Higher Potential for EXCT
EXCT Contact input
(external thermostat off switch)
Lower Potential for EXCT
S3
Keep S3 default setting "NON VOLTAGE",
if digital inputs are to accept non-voltage signals
NON VOLTAGE
VOLTAGE
from dry contacts.
0-140Ω
S4
0-10V
Description
External Potential: 230 V AC, max. 1 A
Internal potential 0 - 75 V DC
Description
External Potential: max. 250 VAC 5 A
Description
Internal Potential: 12 V DC
Internal Potential: 12 V DC
Default pulse signal, can be changed to static by cutting JP001
on A1 PCB
Can be also used as OFF reminder or fire prevention input by
parameter code 00002E (see relevant technical data service
manual for details)
Internal Potential: 5 V DC
AHU Kit – Installation Instructions – 07/2023
GND
+
DI3
+
DI2
+
DI1
-
COM
+
AI
-
+
AO
-