Akd-5-Neutral Sensor Packaging - ABB EntelliGuard AKD-5 Installation Manual

600-2000a retrofill circuit breakers
Hide thumbs Also See for EntelliGuard AKD-5:
Table of Contents

Advertisement

Figure 56. AKD-5—AKT50 2000A Neutral Bus Rogowski ASM 10108216G7
AKD-5—Neutral Sensor Packaging
 Ensure only qualified personnel install, operate, service, and maintain all electrical
equipment.
The Neutral Sensor is constructed using a phase sensor encapsulated appropriately to meet
insulation and durability requirements.
Lead wires are UL-recognized type 18AWG or larger, rated at 600V.
Lead wires are 6 feet in length, minimum.
Lead wires are colored white and black.
The white wire is connected to the "positive" polarity termination.
The black wire is connected to the "negative" polarity termination.
43 EntelliGuard R Circuit Breaker Retrofill AKD-5 Installation Manual
 It must be ensured that the supply power
to the compartment is turned off/
compartment is de-energized for all the
incoming and outgoing circuits of the LVS
prior to any work being conducted on it.
During the installation and related work on
the equipment, it must be ensured that the
operator is using the prescribed PPE for the
specified tasks.
Figure 57. Neutral Bus Rogowski
ASM 10108216G7 Photo
DEH-41547