4.4.5.5 PM2.5 Configuration Points
CfgAlarmPM2.5HighLimit
cfgAlarmPM2.5HighHigh
Limit
CfgAlarmPM2.5Deadband
CfgAlarmPM2.5TimeDelay
CfgPM2.5SensorOffset
SS_MV_OutOfRange_PM2.5
CfgAlarmPM2.5LimitEnable
CfgPM1.0SensorOffset
CfgPM10SensorOffset
TR50 - User Guide
BACnet
Point Name
Instance
151
152
153
154
284
4
24
287
288
Read/
Default
Type
Write
Value
R/W
Analog
35(ug/m
Value
R/W
Analog
55(ug/m
Value
R/W
Analog
5
Value
R/W
Analog
60(s)
Value
R/W
Analog
0
Value
R/W
Multi
1
State
Value
R/W
Multi
4
State
Value
R/W
Analog
0
Value
R/W
Analog
0
Value
Range
0<= PRESENT VALUE of
3
)
cfgAlarmPM2.5HighLimit
<= PRESENT VALUE of
cfgAlarmPM2.5HighHigh
Limit
3
PRESENT VALUE of
)
cfgAlarmPM2.5 HighLimit
<= PRESENT VALUE of
cfgAlarmPM2.5
HighHighLimit <=5000
0 <= PRESENT VALUE of
cfgAlarmPM2.5Deadband
0 <= PRESENT VALUE of
cfgAlarmPM2.5TimeDelay
1: Normal
2: Over high limit
3: Over highhigh limit
1:PM2.5 High Limit And
High High Limit Disable
2:PM2.5 High Limit Enable
3:PM2.5 High High Limit
Enable
4:PM2.5 High Limit And
High High Limit Enable