Honeywell TR50 User Manual page 29

Indoor air quality sensor
Hide thumbs Also See for TR50:
Table of Contents

Advertisement

4.4.5.8 User Interface Configuration
cfgLedRingBrightness
CfgLedRingDimBrightness
CfgLcdBrightness
CfgLcdDimBrightness
CfgLcdAutoCycleTime
cfgLedRingLcdTimeoutTime
cfgLedRingLcdDimTime
CfgIsParaDisplayed
cfgLedRingLcdEnable
CfgLedRingColorOption
24
BACnet
Point Name
Instance
301
302
321
322
341
361
362
381
21
61
Read/
Type
Write
R/W
Analog Value
50
R/W
Analog Value
10
R/W
Analog Value
80
R/W
Analog Value
40
R/W
Analog Value
5(s)
R/W
Analog Value
0(s)
R/W
Analog Value
10(s)
R/W
Analog Value
TR50-5D: 63
TR50-3D: 15
R/W
Binary Value
1
R/W
Multi State
1
Value
Default
Range
Value
40-100
10-40
40-100
10-40
3-10(s)
0(s), 10-30(s)
3-10(s)
For TR50-5D,
cfgIsDisplayed_AQI -
Bit 0
cfgIsDisplayed_Temp -
Bit 1
cfgIsDisplayed_Humi -
Bit 2
cfgIsDisplayed_CO2 -
Bit 3
cfgIsDisplayed_PM2.5 -
Bit 4
cfgIsDisplayed_TVOC -
Bit 5
For TR50-3D,
cfgIsDisplayed_AQI -
Bit 0
cfgIsDisplayed_Temp -
Bit 1
cfgIsDisplayed_Humi -
Bit 2
cfgIsDisplayed_CO2 -
Bit 3
0: Off
1: On
1: Color mode
2: Neutral mode
TR50 - User Guide