Download Print this page
ABB FSCS-21 Quick Installation Manual

ABB FSCS-21 Quick Installation Manual

Cip safety functions module

Advertisement

Quick Links

OPTIONS FOR ABB DRIVES
FSCS-21 CIP Safety™ functions module
Quick installation guide
Related manual
FSCS-21 CIP Safety™ functions module user's manual (3AXD50001065478 [English])
Safety instructions
WARNING
damage to the equipment can occur.
Description of the FSCS-21 module
The FSCS-21 module adds support for the EtherNet/IP™ communication protocol and the CIP Safety™
extensions. With the module, you can connect the drive to a programmable logic controller (PLC). The
module supports the Safe torque off (STO) and Safe stop 1 with time monitoring (SS1-t) safety functions
with CIP Safety over EtherNet/IP.
Intentional misuse
Use the module according to the instructions given in the applicable manuals. ABB is not responsible for
any damage caused by the misuse of the module. The module is not designed to protect a machine
against intentional misuse or sabotage.
Limitations for use
Use the module only in an environment that meets the requirements given in the drive hardware manual.
Do not use the module in an environment that has conductive dust in the air. If you use the module in an
environment that does not meet the requirements, equipment malfunction or loss of a safety function
can occur.
Drive compatibility
ACS880 drives with primary control program version 2.90 or later
ACS580 drives with primary control program version 2.07 or later
ACS380 drives with primary control program version 2.07 or later
Layout of the module
1
EtherNet/IP™
CIP Safety™
2
3
4
5
Obey the safety instructions of the drive. If you ignore them, injury or death, or
No. Description
1
Lock
2
Grounding screw
3
RJ-45 connector [X1] to Ethernet
7
4
RJ-45 connector [X2] for chaining another module
5
STO connector (under connectors [X1] and [X2])
6
Diagnostic LEDs
6
7
MAC address

Advertisement

loading

Summary of Contents for ABB FSCS-21

  • Page 1 Intentional misuse  Use the module according to the instructions given in the applicable manuals. ABB is not responsible for any damage caused by the misuse of the module. The module is not designed to protect a machine against intentional misuse or sabotage.
  • Page 2 Mechanical installation If you have an ACS380 drive and order FSCS-21 separately as a kit, you must replace the ACS380 standard cover with the optional deeper cover (ordering code: 3AXD50000190188). For more information on the deeper cover, visit https://new.abb.com/products/3AXD50000190188/3axd50000190188 Install the module mechanically as follows: De-energize the drive and isolate it from dangerous voltages.