Hitachi SJ300 Series Quick Reference Manual page 17

Hide thumbs Also See for SJ300 Series:
Table of Contents

Advertisement

Error
Code
Inverter thermal trip
E21
E23
Gate array error
Phase failure detection
E24
E30
IGBT error
E35
Thermistor
Brake error
E36
– – – –
Under-voltage (brownout)
with output shutoff
Automatic restart and phase
loss
Expansion card #1 error
E6X
Expansion card #2 error
E7X
Error Status Codes and Error Trip Conditions
The digit to the right of the decimal point in the error code (such as
indicates inverter status at the moment the error occurred. Use the Up and
Down arrow keys to scroll through the trip condition parameters.
Status
Inverter
Code
Status
Reset
---.0
Stop
---.1
Deceleration
---.2
---.3
Constant
speed
Acceleration
---.4
Name
Status
Inverter
Code
f0 stop
---.5
Starting
---.6
DC braking
---.7
---.8
Overload
restriction
15
Probable Cause(s)
• Inverter internal temperature is above
the threshold
• An internal inverter error has occurred
(CPU / gate array IC)
• One of three lines of the 3-phase
power is missing
• Instantaneous over-current on any
IGBT (output transistor) device
• Thermistor input, [TH] and [CM1], is
over the temp. threshold
• The state of the external brake was not
detected within the waiting time (set by
parameter B024)
• Low input voltage caused the inverter
to turn OFF the motor output and try to
restart. If unsuccessful, a trip occurs.
• Inverter is restarting, due to an over-
current, over-voltage, under-voltage, or
a phase loss event.
• An error has occurred in an
expansion card or at its connecting
terminals. Please refer to the manual for
the expansion card for additional details.
Status
1
2
E01.4
Trip Conditions
Error code
Output frequency
Motor current
DC bus voltage
Cumulative op. time
Cumulative ON time
)