3. Functional description

In this section, functions added by the installation of this F10M option unit, on top of the standard inverter
functions, are described.

3.1 F10M communication function

Through the communication network, drive and stop control and concentrated monitoring control of operation
status can be carried out by the programmable controller and industrial computer.

3.1.1 Connection of transmission cable

SL1, SL2, SG
Transmission path is constructed by the shielded twisted pair cables as shown in the figure below.
Be sure to connect SL1, SL2 and SG mutually to another station. Note that wrong connection will not bring the
correct transmission.
SHD
Connect a shield of twisted pair cable to the transmission terminal SHD of each station and set up a class 3 or
equivalent grounding work in an arbitrary station.
Terminal resistor
Set terminal resistors at both sides of the system for the sake of impedance matching. Connect terminal
resistor (120Ω-1/2W) between the terminal block SL1 and SL2.
(As for the master station (MS), terminal resistor can be combined by connecting L1 and TERM.)
Grounding / Earthing
(Grounding / earthing resistance 100
Connection of communication cable of TOSLINE F10M
Signal name
Do not connect a grounding line of the shield and a power line earth of the inverter or so.
Separate a transmission cable from the main circuit connection wire by more than 200mm.
Shielded twisted pair cable
SL1
Transmitting and receiving data
SL2
Transmitting and receiving data
SG
Signal ground
max.)
Name
10
E6580772
Terminal resistor
120
-1/2W
Detail
Positive line
Negative line
Ground of signal line