Cable sized for neutral current=1.7Xphase current. Size cable appropriate to actual load type: balanced, unbalanced, non-linear.
4
TABLE 11.6 RECOMMENDED CABLE SIZE AND FASTENER TORQUE FOR 300 KVA UPS
Bus Number
75 °C Copper Wire
1
(2) 250 kcmil – (3) 2/0
2
(2) 250 kcmil – (3) 2/0
3
(2) 250 kcmil – (3) 2/0
4
(4) 300 kcmil – (4) 350 kcmil
1
5
(4) 300 kcmil – (4) 350 kcmil
1
6
(2) 300 kcmil – (3) 2/0
7
(2) 300 kcmil – (3) 2/0
8
(2) 300 kcmil – (3) 2/0
9
(2) 300 kcmil – (3) 2/0
4
10
(2) 300 kcmil – (3) 2/0
11
(4) 300 kcmil – (4) 350 kcmil
12
(4) 300 kcmil – (4) 350 kcmil
Flywheel Input (+)
3
One battery string. (Consult factory if using more than one battery string.)
1
Fastener torque specified for: 1/2 in. diameter grade 5 steel bolt.
2
Per flywheel unit
3
Cable sized for neutral current=1.7Xphase current. Size cable appropriate to actual load type: balanced, unbalanced, non-linear.
4
TABLE 11.7 RECOMMENDED CABLE SIZE AND FASTENER TORQUE FOR 500 KVA UPS
Bus Number
75 °C Copper Wire
1
(3) 250 kcmil – (3) 400 kcmil
2
(3) 250 kcmil – (3) 400 kcmil
3
(3) 250 kcmil – (3) 400 kcmil
4
(3) 400 kcmil – (3) 500 kcmil
5
(3) 400 kcmil – (3) 500 kcmil
6
(3) 400 kcmil – (3) 500 kcmil
7
(6) 400 kcmil – (6) 500 kcmil
2
8
3
9
(3) 400 kcmil – (3) 500 kcmil
10
(3) 400 kcmil – (3) 500 kcmil
11
(3) 400 kcmil – (3) 500 kcmil
12
(6) 400 kcmil – (6) 500 kcmil
2
13
(3) 400 kcmil – (3) 500 kcmil
14
(3) 400 kcmil – (3) 500 kcmil
Fastener torque specified for: 1/2 in. diameter grade 5 steel bolt.
1
Cable sized for neutral current=1.7Xphase current. Size cable appropriate to actual load type: balanced, unbalanced, non-linear.
2
Ground cables
3
38
Cable Size (Min-Max)
90 °C Copper Wire
(4) 300 kcmil – (4) 350 kcmil
(4) 300 kcmil – (4) 350 kcmil
(2) 250 kcmil – (3) 1/0
(2) 250 kcmil – (3) 1/0
(2) 250 kcmil – (3) 1/0
(2) 250 kcmil – (3) 1/0
(2) 250 kcmil – (3) 1/0
(4) 250 kcmil – (4) 300 kcmil
(4) 250 kcmil – (4) 300 kcmil
(2) AWG 2/0
Cable Size (Min-Max)
90 °C Copper Wire
(3) 4/0 kcmil – (3) 250 kcmil
(3) 4/0 kcmil – (3) 250 kcmil
(3) 4/0 kcmil – (3) 250 kcmil
(4) 400 kcmil – (4) 500 kcmil
(4) 400 kcmil – (4) 500 kcmil
(3) 400 kcmil – (3) 500 kcmil
(3) 400 kcmil – (3) 500 kcmil
1/0
(3) 400 kcmil – (3) 500 kcmil
(3) 400 kcmil – (3) 500 kcmil
(3) 400 kcmil – (3) 500 kcmil
(3) 400 kcmil – (3) 500 kcmil
(3) 400 kcmil – (3) 500 kcmil
(3) 400 kcmil – (3) 500 kcmil
(2) 4/0 – (3) 1/0
540 in.-lb. (61 N•m)
(2) 4/0 – (3) 1/0
540 in.-lb. (61 N•m)
(2) 4/0 – (3) 1/0
540 in.-lb. (61 N•m)
540 in.-lb. (61 N•m)
540 in.-lb. (61 N•m)
540 in.-lb. (61 N•m)
540 in.-lb. (61 N•m)
540 in.-lb. (61 N•m)
540 in.-lb. (61 N•m)
540 in.-lb. (61 N•m)
540 in.-lb. (61 N•m)
540 in.-lb. (61 N•m)
(2) AWG 2/0
300 in.-lb. (33.9 N•m)
540 in.-lb. (61 N•m)
540 in.-lb. (61 N•m)
540 in.-lb. (61 N•m)
540 in.-lb. (61 N•m)
540 in.-lb. (61 N•m)
540 in.-lb. (61 N•m)
540 in.-lb. (61 N•m)
1/0
540 in.-lb. (61 N•m)
540 in.-lb. (61 N•m)
540 in.-lb. (61 N•m)
540 in.-lb. (61 N•m)
540 in.-lb. (61 N•m)
540 in.-lb. (61 N•m)
540 in.-lb. (61 N•m)
G8000 Series Installation and Operation Manual
Tightening
Torque
2
Tightening
Torque
1