The procedure to stop the UPS is shown in Steps 1-3.
LED Key
- LED Off
- LED On
- LED Flash
BYPASS
AC - Vo 480 V
AC - Io 50%
PRESS 'UPS' SWITCH
AC INPUT
CONVERTER
FLOAT CHARGE
EQUAL CHARGE
BATTERIES
DISCHARGE
BYPASS INPUT
BYPASS
MOVE #72B TO 'OFF' POSITION
CONVERTER
AC INPUT
FLOAT CHARGE
EQUAL CHARGE
BATTERIES
DISCHARGE
BYPASS INPUT
BYPASS
PRESS 'RUN' SWITCH
CONVERTER
AC INPUT
FLOAT CHARGE
EQUAL CHARGE
BATTERIES
DISCHARGE
BYPASS INPUT
66
UPS
INVERTER
AC
SWITCH
AC OUTPUT
BYPASS
UPS
INVERTER
AC
SWITCH
AC OUTPUT
BYPASS
UPS
INVERTER
AC
SWITCH
AC OUTPUT
BYPASS
STEP 1
Transfer to Bypass supply as described in
Switch Power Supply.
UPS LED is "OFF".
BYPASS LED is "ON".
STEP 2
Turn off the DC Input Breaker (72B) on
the external battery cabinet, and, press
the G8000 "STOP" button for at least 0.5
seconds.
BATTERIES LED is "OFF".
INVERTER LED flashes then "OFF".
FLOAT CHARGE LED and CONVERTER
LED are "OFF".
STEP 3
Wait until procedure is completed.